Product Features
1. Turn-key Solution
All-in-one device integrating inverter, transformer, HV and LV switchgear. No on-site installation is required.
Container-type enclosure, easy to transport and load without the special lifting equipment.
2. Strong Environmental Adaptability
Anti-corrosion, high-strength steel enclosure.
Flame-proof with stable temperature functions and thermal insulation.
Excellent ventilation, sand, and dust-proof capabilities.
3. High Reliability and Safety
The cast-resin dry-type transformer inside the substation is fireproof, explosion-proof, and flame-resistant.
Certified C2, E2, and F1 testing standards.
Cost Reduction and Efficiency Improvement:
Lower investment and higher returns.
Saves 15% to 20% of total investment compared to traditional "inverter room + step-up station."
Reduces the number of foundations from two to one, saving 50% of installation time.
Copper connections between inverters and transformers eliminate the need for cables between the inverter room and the transformer. Structural optimization also reduces the requirement for two low-voltage switchgear units between the inverter and transformer.
4. Flexible Design: Can be customized according to customer site conditions.
General Layout A
General Layout B
Datasheet
Performance | |||
Type | ZD-1000-OD/35 | ZD-2000-OD/35 | |
Incoming Data | |||
Max DC incoming power | 1123KW | 1123KW×2 | |
Max Array Trip Voltage | 1000Vdc | 1000Vdc | |
Incoming working voltage range | 750~1000Vdc | 750~1000Vdc | |
Max incoming current | 1130A*2 | 1439A×2 | |
Numbers of DC incoming branch | 10~20 lines | 20~30 lines | |
Outgoing Data | |||
Rated outgoing Power | 500+500KW | 1000KW×2 | |
Inverter outgoing voltage | 315Vac | 500Vac | |
Transformer outing voltage | 37KV | 37KV | |
Transformer outgoing current | 16.5A | 33A | |
System Characteristics | |||
Transformer Type | Two Windings | Dual outing windings | |
HV SWG | Voltage and current display; surge arrestor; earthing switch; protection fuse | Voltage and current display; surge arrestor; earthing switch; protection fuse | |
LV CT、PT and power meter | Optional | Optional | |
Transformer thermometer remote control | Optional | Optional | |
IP Grade | IP54 | IP54 |