| Availability: | |
|---|---|
| Quantity: | |
1. International Export Proven: Engineered to meet IEC 62271-202 and EN standards, our units are already operational in North American and British grids, ensuring compliance with international safety and performance benchmarks.
2. Rapid Deployment: Factory-assembled and pre-commissioned. Reduce your on-site installation time by up to 80% compared to traditional civil works.
3. Space Efficiency: Features a compact footprint (only 1/10th the size of conventional stations), making it ideal for dense urban areas, London-style residential developments, or restricted industrial sites.
4. Extreme Resilience: Built with high-grade, anti-corrosive materials (IP54/IP65) to withstand diverse climates—from the humid coastal air of the UK to the temperature extremes of the American Midwest.
| Feature | Specification Details |
| Voltage Range | Primary up to 35kV; Secondary tailored to local grid requirements. |
| Transformer Choice | Available with CEEG’s DuPont Nomex® insulated dry-type or high-efficiency oil-immersed transformers. |
| Enclosure Materials | Aluminum alloy, stainless steel, or GRC (Glass Fiber Reinforced Cement) for architectural blending. |
| Smart Integration | Fully compatible with SCADA and remote monitoring systems for real-time diagnostics. |
Enhanced Safety: Equipped with a "Five-Proof" mechanical/electrical interlocking system to prevent operator error.
Low Maintenance: Specialized ventilation and dust-proof designs ensure long-term reliability with minimal site visits.
Environmental Harmony: Quiet operation and customizable exterior finishes allow for seamless integration into parks, city centers, or commercial districts.
Renewables: Solar and wind farm step-up stations.
Public Utilities: Municipal power distribution and smart city grids.
Industrial: Mining, oil & gas, and manufacturing facilities.


No. |
Items |
Technical Parameter |
Specification |
1 |
|
Altitude |
<2000m |
2 |
Temperature Range |
-25 - +40℃ |
|
3 |
Relative Humidity |
0-95% |
|
4 |
Anti-Corrosion Level |
C4/C5 |
|
5 |
IP Protection |
IP54 |
|
6 |
|
Capacity |
500-10000kVA |
7 |
Vector Group |
Dy11 |
|
8 |
Turns Ratio |
0.4(0.69)KV/10(20)(35)kV |
|
9 |
Efficiency |
Tier1/Tier2 |
|
10 |
Cooling Method |
AN/AF |
|
11 |
Corrosion Protection Classes |
C4 |
|
12 |
Compliant Standard |
IEC 62271-202 |
|
13 |
Non-Electrical Protection for Transformers |
Yes |
|
14 |
High Voltage Cabinet |
Wiring |
Cable Entry: Bottom / Cable Exit: Bottom |
15 |
Grid Connection Voltage Levels |
12KV , 24kV,40.5KV |
|
16 |
|
Auxiliary Transformer Capacity |
40-200kVA |
17 |
Auxiliary Transformer Vector Group and Voltage Ratio |
Dyn11 |
|
18 |
Required Power and Number of Battery String Circuits |
As required |
|
19 |
UPS Capacity and Backup Duration |
As required |
|
20 |
EMS&Communication(optional) |
Communication Topology of the Energy Storage Power Station: |
IEC 61850 or Modbus TCP |
21 |
Switch Communication Configuration |
20 electrical ports, 100Mbps |
|
22 |
Acceptance Standards |
Compliant with IEC, EN, and GB standards |